Application Brochure

© 2013 284_A - 02/13 2 of 12
Modbus
®
/ BACnet
®
IP
483
tekmarNet
®
4
S3
P2
P1
P8
P7
S2
S8S7S6
P3 P4 P5 P6
S5
S9
S4
F1
284
S1
C.A. Damper
BAS
C.A. Proof
Application A 284-1 Mechanical
Description
Two single stage non-condensing boilers & two modulating condensing boilers are operated to provide a boiler target
temperature for space heating, indirect DHW and setpoint loads. The boiler target temperature for the space heating load
is determined from outdoor temperature reset.
Concept Drawing: This is only a concept drawing, not an engineered drawing. It is not intended to describe a complete system, nor any particular system. It is up to the
system designer to determine the necessary components for and configuration of the particular system being designed, including additional equipment, isolation relays
(for loads greater than the control’s specified output ratings), and any safety devices which in the judgement of the designer are appropriate, in order to properly size,
configure and design that system and to ensure compliance with building and safety code requirements.
Features:
The boiler plant is sequenced to obtain maximum efficiency based on the boiler types & target temperatures. For detailed
information about sequencing, rotation & staging, refer to the 284_D Installation & Operation Manual.
Dual primary pumps with a flow proof provide redundancy. Pumps can be sequenced with equal run-time rotation.
A flow sensor is used to prove flow for the primary pumps. The flow sensor is also used for energy monitoring.
System includes a combustion air (C.A.) damper. Proving of C.A. damper via external C.A. proof (motor end switch).
Boiler ∆T monitoring is available when using optional boiler outlet sensors (S6 to S9) & boiler inlet sensor (S5).
Remote monitoring from the Internet is available through the tN4 Gateway 483.
Communication with a Building Automation System (BAS) is available using BACnet
®
or Modbus
®
.
ENABLE (1) = AUTO
CONDENSE (1) = NO
Boil TYPE (1) = 1STG
ENABLE (2) = AUTO
CONDENSE (2) = NO
Boil TYPE (2) = 1STG
ENABLE (3) = AUTO
CONDENSE (3) = YES
Boil TYPE (3) = MOD
ENABLE (4) = AUTO
CONDENSE (4) = YES
Boil TYPE (1) = MOD
Essential Source (#) Settings:
S1 = Outdoor Sensor
S2 = Boiler Supply Sensor
S3 = Boiler Return Sensor
S4 = DHW Sensor
S5 = Boiler Inlet Sensor
S6-S9 = Boiler Outlet Sensors
F1 = Flow Sensor
P1, P2 = Primary Pumps
P3-P6 = Boiler Pumps
P7 = IDHW Pump
P8 = Setpoint Pump
Legend
DIP Settings:
External Flow Proof / Off
External C.A. Proof / Off
Off / Exercise
Setback / Off
Essential System Settings:
APP MODE = RSET
AUX RELAY = DMPR
PUMP 1 = AUTO
PUMP 2 = AUTO
IDHW MODE = ON
IDHW LOCATION = Boil
IDHW SENSOR = ON
IDHW PRIM PUMP = OFF
SETP MODE = ON
SETP PRIM PUMP = OFF
FLOW SENSOR = ON
FLOW PROOF = 1 to 100%