Application Brochure

© 2013 284_A - 02/13 4 of 12
P2
P1
Current Switch
Current Switch
S2
S3S5
S8
S7
P3 P4 P5 P6
S9
284
S1
S6
P7
S4
S1 = Outdoor Sensor
S2 = Boiler Supply Sensor
S3 = Boiler Return Sensor
S4 = DHW Sensor
S5 = Boiler Inlet Sensor
S6-S9 = Boiler Outlet Sensors
P1, P2 = Primary Pumps
P3-P6 = Boiler Pumps
P7 = IDHW Pump
Application A 284-2 Mechanical
Description
Four modulating condensing boilers are operated to provide an outdoor temperature reset boiler target for a space heating
load. The fourth boiler also operates to provide heat for an indirect DHW load with priority over space heating.
Concept Drawing: This is only a concept drawing, not an engineered drawing. It is not intended to describe a complete system, nor any particular system. It is up to the
system designer to determine the necessary components for and configuration of the particular system being designed, including additional equipment, isolation relays
(for loads greater than the control’s specified output ratings), and any safety devices which in the judgement of the designer are appropriate, in order to properly size,
configure and design that system and to ensure compliance with building and safety code requirements.
Features:
The boiler plant is sequenced to obtain maximum efficiency based on the boiler types & target temperatures. For detailed
information about sequencing, rotation & staging, refer to the 284_D Installation & Operation Manual.
Dual primary pumps with a flow proof provide redundancy. Pumps can be sequenced with equal run-time rotation.
Boiler ∆T monitoring is available when using optional boiler outlet sensors (S6 to S9) and boiler inlet sensor (S5).
The boiler outlet sensor S9 is required for indirect DHW operation.
ENABLE (1) = AUTO
CONDENSE (1) = YES
Boil TYPE (1) = MOD
ENABLE (2) = AUTO
CONDENSE (2) = YES
Boil TYPE (2) = MOD
ENABLE (3) = AUTO
CONDENSE (3) = YES
Boil TYPE (3) = MOD
ENABLE (4) = AUTO
CONDENSE (4) = YES
Boil TYPE (4) = MOD
Essential Source (#) Settings:
APP MODE = RSET
PUMP 1 = AUTO
PUMP 2 = AUTO
IDHW MODE = ON
IDHW LOCATION = NEAR
IDHW SENSOR = ON
Essential System Settings:
Legend
DIP Settings:
External Flow Proof / Off
External C.A. Proof / Off
Off / Exercise
Setback / Off