Installation

25 of 36 © 2001 D 364 - 07/01
364 View Menu (2 of 2)
364 Adjust Menu (1 of 5)
Item Field
Access
Level
Description
Range
Actual
Setting
Section
LTD
USER
INST
ADV
OFF, 20 to 95°F
(OFF, -7 to 35°C)
Default = OFF
E2
E3
OFF,
0:30 to 17:00 hr,
INF (Infinite)
Default = 4:00 hr
E1
If a slab sensor is used, this item is the desired
slab surface temperature while in the melting
mode. If no slab sensor is used, this item is
the theoretical slab surface temperature while
in the melting mode.
DIP switch = Snow Melting
This item is the desired slab surface tempera-
ture while in the idling mode.
DIP switch = Snow Melting
This item is the time that the slab is operated for
once it has reached the MELTING temperature.
This item can only be viewed if a Remote Start
/ Stop Module 039 has not been connected.
DIP switch = Snow Melting
32 to 95°F
(0 to 35°C)
Default = 36°F (C)
E2
E3
Item Field
Access
Level
Description
Range
Section
LTD
USER
INST
ADV
-31 to 266°F
(-35 to 130°C)
F1
-31 to 266°F
(-35 to 130°C)
F2
---, OFF, 100 to 220°F
(OFF, 38 to 104°C)
C1
---, OFF, 70 to 190°F
(OFF, 21 to 88°C)
C1
-31 to 266°F
(-35 to130°C)
C1
Target boiler supply is the temperature the control is cur-
rently trying to maintain at the boiler sensor ±1/2 of the
differential.
Boil SENS = SUP
Current boiler supply water temperature as measured by
the boiler sensor.
Boil SENS = SUP
Current boiler return water temperature as measured by
the boiler sensor.
Boil SENS = RET
Minimum boiler supply temperature during a DHW
demand.
DHW SENS = NONE, DHW THRU NONE,
Boil SENS = SUP
Target DHW tank temperature.
DHW SENS = DHW, DHW THRU NONE
Current DHW tank temperature.
DHW SENS = DHW, DHW THRU NONE
---, 1 to 255°F
(-17 to 124°C)
F1