Installation

© 2001 D 364 - 07/01 28 of 36
Item Field
Access
Level
Description
Range
Actual
Setting
Section
LTD
USER
INST
ADV
364 Adjust Menu (4 of 5)
LITE, MED, HEVY
Default = MED
F1
AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO
F1
NONE, PUMP,
VALV
Default = PUMP
C1
NONE, DHW
Default = NONE
C1
OFF, 70 to 190°F
(OFF, 21 to 88°C)
Default = 140°F (60°C)
C1
OFF, 100 to 220°F
(OFF, 38 to
104°C)
Default = 180°F (82°C)
C1
NONE, MIX, B+M
Default = NONE
C2
OFF, 70 to 220°F
(OFF, 21 to 104°C)
Default = 180°F (82°C)
C4
35 to 100°F, O FF
(2 to 38°C, OFF)
Default = 70°F (21°C)
A
OFF,
0:10 to 40:00 min
Default = 0:20 min
F1
The time delay that the control can expect
between the time the boiler contact closes and
the burner fires.
Boil SENS = SUP
The thermal mass characteristics of the boiler
that is being used.
Boil SENS = SUP
The differential that the control is to use when
it is operating the boiler.
Boil SENS = SUP
The device that is being used to supply flow to
the heat exchanger in the DHW storage tank.
Selects whether or not a DHW sensor is being
used to measure the DHW tank temperature.
DHW THRU NONE
The desired DHW storage tank temperature.
DHW THRU NONE, DHW SENS = DHW
The minimum boiler supply temperature to the
DHW storage tank.
DHW THRU NONE, DHW SENS = NONE,
Boil SENS = SUP
The portions of the heating system that the
DHW will have priority over.
DHW THRU NONE
The minimum boiler supply temperature when
a setpoint demand is present.
Boil SENS = SUP AND DHW SENS = DHW
OR DHW THRU = NONE
The systems warm weather shut down
temperature.
The maximum length of time that the primary
pump will continue to run after all of the
demands have been removed.
0:00 to 3:00 min
Default = 0:10 min
F1