Installation
 © 2001   D 364 - 07/01  28 of 36 
Item Field
Access
Level
Description
Range
Actual 
Setting
Section
LTD
USER
INST
ADV
364 Adjust Menu (4 of 5)
LITE, MED, HEVY
Default = MED
F1
AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO
F1
NONE, PUMP, 
VALV
Default = PUMP
C1
NONE, DHW
Default = NONE
C1
OFF, 70 to 190°F
(OFF, 21 to 88°C)
Default = 140°F (60°C)
C1
OFF, 100 to 220°F
(OFF, 38 to 
104°C)
Default = 180°F (82°C)
C1
NONE, MIX, B+M
Default = NONE
C2
OFF, 70 to 220°F
(OFF, 21 to 104°C)
Default = 180°F (82°C)
C4
35 to 100°F, O FF
(2 to 38°C, OFF)
Default = 70°F (21°C)
A
OFF, 
0:10 to 40:00 min
Default = 0:20 min
F1
The time delay that the control can expect 
between the time the boiler contact closes and 
the burner fires.
Boil SENS = SUP
The thermal mass characteristics of the boiler 
that is being used.
Boil SENS = SUP
The differential that the control is to use when 
it is operating the boiler.
Boil SENS = SUP
The device that is being used to supply flow to 
the heat exchanger in the DHW storage tank.
Selects whether or not a DHW sensor is being 
used to measure the DHW tank temperature. 
DHW THRU ≠ NONE
The desired DHW storage tank temperature.
DHW THRU ≠ NONE, DHW SENS = DHW
The minimum boiler supply temperature to the 
DHW storage tank.
DHW THRU ≠ NONE, DHW SENS = NONE, 
Boil SENS = SUP
The portions of the heating system that the 
DHW will have priority over.
DHW THRU ≠ NONE
The minimum boiler supply temperature when 
a setpoint demand is present.
Boil SENS = SUP AND DHW SENS = DHW 
OR DHW THRU = NONE
The system’s warm weather shut down 
temperature.
The maximum length of time that the primary 
pump will continue to run after all of the 
demands have been removed.
0:00 to 3:00 min
Default = 0:10 min
F1