Installation

31 of 36 © 2001 D 364 - 07/01
When troubleshooting any heating system, it is a good idea to establish a set routine to follow. By following a consistent routine, many
hours of potential headaches can be avoided. Below is an example of a sequence that can be used when diagnosing or troubleshoot-
ing problems in a hydronic heating system.
Troubleshooting
Establish the problem. Get as much information from the customer as possible about the prob-
lem. Is there too much heat, not enough heat, or no heat? Is the problem only in one zone or does
the problem affect the entire system? Is this a consistent problem or only intermittent? How long
has the problem existed for? This information is critical in correctly diagnosing the problem.
Understand the sequence of operation of the system. If a particular zone is not receiving enough
heat, which pumps or valve in the system must operate in order to deliver heat to the affected
zone? If the zone is receiving too much heat, which pumps, valves or check valves must operate
in order to stop delivery of heat?
Press the Test button on the control and follow the control through the test sequence as
described in the Testing section. Pause the control as necessary to ensure that the correct device
is operating as it should.
Sketch the piping of the system. This is a relatively simple step that tends to be overlooked,
however it can often save hours of time in troubleshooting a system. Note flow directions in the
system paying close attention to the location of the pumps, check valves, pressure bypass valves
and mixing valves. Ensure correct flow direction on all pumps. This is also a very useful step if
additional assistance is required.
Document the control for future reference. Before making any adjustments to the control, note
down all of the items that the control is currently displaying. This includes items such as error
messages, current temperatures and settings, and which devices should be operating as indi-
cated by the LCD. This information is an essential step if additional assistance is required to
diagnose the problem.
Isolate the problem between the control and the system. Now that the sequence of operation is
known and the system is sketched, is the control operating the proper pumps and valves at the
correct times? Is the control receiving the correct signals from the system as to when it should
be operating? Are the proper items selected in the menus of the control for the device that is to
be operated?
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving
adequate voltage to the power terminals and the demand terminals as noted in the technical data.
Use the multimeter to determine if the internal contacts on the control are opening and closing
correctly. Follow the instructions in the Testing the Wiring section to simulate the closed contacts
on the terminal blocks as required. Test the sensors and their wiring as described in the sensor
Data Brochures.
Monitor the system over a period of time. Select the applicable items in the Monitor menu of the
control and reset them to zero. Allow the system and the control to operate over a known period
of time and then record the Monitor items. Use the information to help diagnose any remaining
problems.
Establish the
Problem
Understand
the Sequence
of Operation
Use the Test
Routine
Sketch the
Piping in the
System
Document the
Control
Isolate the
Problem
Test the
Contacts
Voltages &
Sensors
Monitor the
System