Installation

© 2001 D 364 - 07/01 32 of 36
Error Displayed
Description of Error
364 Error Messages (1 of 3)
The control was unable to store a piece of information into its EEPROM. This error can be caused by a
noisy power source. The control will display the error message and will continue to operate as normal.
Pressing either the Menu or Item button will clear this error.
The control was unable to read a piece of information stored in the Adjust menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust menu. The control
will stop operation until all of the items available in the Adjust menu of the control have been checked
by the user or installer. Note: Access level must be set to ADV in order to clear the error.
The control was unable to read a piece of information stored in the Miscellaneous menu. Because of
this, the control was required to load factory settings into all of the items in the Miscellaneous menu.
The control will continue to display the error message until all of the items available in the Misc menu
of the control have been checked by the user or installer. Note: Access level must be set to ADV in
order to clear the error.
The control was unable to read a piece of information from the A/D system. This is the system that the
control used to read the sensor inputs. If this error occurs, it is an indication that the sensor wires have
been run in a noisy electrical environment. To clear this error, press either the Menu or Item button.
The control will stop operation until the A/D fault is corrected.
An incorrect device has been connected to the tekmar Net (tN2) input terminal. To correct this error,
ensure that the correct device is being used. Once the problem has been corrected, press either the
Menu or Item button to clear the error message from the control.
A short circuit has been read between the tekmar Net (tN2) and a Com terminal on the control. Either
the wires leading to the tekmar Net (tN2) device are shorted or the polarity of the wires is reversed.
Determine the cause and remove the short. The error message can be cleared by pressing either the
Menu or Item button.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control
assumes an outdoor temperature of 32°F and continues operation. Locate and repair the problem as
described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control
assumes an outdoor temperature of 32°F and continues operation. Locate and repair the problem as
described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
The control is no longer able to read the mix supply sensor due to a short circuit. In this case, the
control operates the mixing device at a fixed output as long as there is a mixing demand. Locate and
repair the problem as described in the Data Brochure D 070. To clear the error message from the
control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the mix supply sensor due to an open circuit. In this case, the
control operates the mixing device at a fixed output as long as there is a mixing demand. Locate and
repair the problem as described in the Data Brochure D 070. To clear the error message from the
control after the sensor has been repaired, press either the Menu or Item button.