Installation Pocket Guide

Product design, software and literature are Copyright © 2010 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
4 of 4
All specifications are subject to change without notice.
Printed in Canada. Q 400 - 09/10.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Head Of ce: 5100 Silver Star Road,
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
Press menu button until the Adjust Menu is displayed. Press item
button to locate the desired setting.
Item Field Range Access Description Set to
ADJUST
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
Installer
OUTDOOR DESIGN
Typically set to the temperature of the coldest day of
the year. The outdoor air temperature used in the boiler
heating curve is used to determine the boiler target
temperature.
EMS2,
EMS1,
4-20
0-10,
2STG,
1STG
Default = 1STG
Installer
BOILER TYPE
The type of boiler connected to the control.
1STG = single one-stage on-off boiler
2STG = single two-stage on-off boiler
0-10 = 0-10 V (dc) modulating boiler
4-20 = 4-20 mA modulating boiler
EMS1 = tekmar boiler staging controls
EMS2 = Viessmann modulating boilers with
OpenTherm
VIEW
70 to 200°F
(21.0 to 93.5°C)
Default = 180
°F
(82.0°C)
Installer
BOILER DESIGN
The supply water temperature required for the boiler
zones to heat the building on the typical coldest day
of the year. Recommendations:
High mass radiant floor = 120°F (50°C)
Low mass radiant floor = 140°F (60°C)
Fancoil or air handling unit = 190°F (90°C)
Copper fin-tube convector = 180°F (80°C)
Radiators = 160°F (70°C)
Low profile baseboard = 150°F (65°C)
Critical Settings11.