Fan Operation
Section E
The fan operates together with the air heating or cooling systems. The user can also
select to operate the fan manually by pressing the Fan button. This allows the user to
choose between Auto and On. “Auto” allows the fan to operate together with heating or
cooling but normally the fan is off. “On” forces the fan to operate continuously.
Ventilation Fan
------------------------------------------------------
------------------------------------------------------
In order to provide ventilation to the building, the fan can also operate for additional
time beyond what is required for the heating and cooling systems. Ventilation allows the
user to select the fan to operate for a minimum percentage out of each hour. Options
are 10 to 90%, in 10% (6 minutes per hour) increments, as well as Auto and On. This
is available when the Vent Mode setting in the Setup menu is set to On.
Once Ventilation is set to On, the Fan minimum run time percentage during the and
events can be set so that the fan can operate on a schedule and/or together with scenes.
Fan Post Purge
------------------------------------------------------
------------------------------------------------------
The fan relay includes a post purge feature that operates the fan after the heating or
cooling system has shut off. When a duct temperature sensor is installed the length
of post purge is based on the air duct temperature and the Heatpurge or Coolpurge
temperature settings. When there is no duct temperature sensor installed, the length
of post purge is based upon the Heatpurge and Coolpurge time settings.