User's Guide

Breeze/Breeze-V/Vivid+ User Guide T0007805_UG Version 1.2
TEKTELIC Communications Inc. Page 10 of 22
Parameter
Specification
Sensor Lifetime
Breeze model with optimum settings and baseline use case:
1
> 5.5 years with 2xAA LTC batteries
Vivid+ model with optimal settings and baseline use case:
> 4.7 years with 2xAA LTC batteries
Breeze-V model with optimal settings and baseline use case:
> 4.6 years with 2xAA LTC batteries
Maximum transmit power
LoRa: 15 dBm
GFSK: 0 dBm
Number of indicator LEDs
4 (2 green, 1 yellow, and 1 red)
Measurement sensing functions
Temperature, humidity, light, pressure, CO
2
Detection sensing functions
Human movement
Temperature measurement accuracy
< ±0.3°C between 0°C and 5°C
±0.2°C between 5°C and 60°C
Humidity measurement accuracy
< ±4% between 0% and 100%
±2% between 20% and 80%
Light sensitivity
Detection of weak light to typical work light conditions (5 lux to
1000 lux)
2
Peak sensitivity at 550 nm
Pressure measurement accuracy
< ±2 hPa between 300 hPa and 1100 hPa
CO
2
concentration measurement
accuracy
±30 ppm +3% of reading between 400 ppm and 5000 ppm
Extended range ±10% of reading for an extended range of up to
10000 ppm
3
Motion detection
Pyroelectric infrared sensor
Ceiling mount:
X-angle: 104° (no mask)
Y-angle: 104° (no mask)
Height: 3 m (no mask)
1.3 Transducer Details
1.3.1 Temperature/Humidity Transducer
The Breeze/Breeze-V/Vivid+ includes a combination temperature/humidity transducer from
Sensirion (SHTC3). It is a small footprint, very low power device. It features operation over I
2
C
protocol and operates from 0% to 100% RH and -40°C to 125°C with a typical accuracy of ±2%
RH and ±0.2°C. The typical and maximum accuracies specified across the operating relative
1
Baseline use case assumes room temperature, LoRa Tx power of 15 dBm, LoRa SF 10, and LoRa BW of 125 kHz.
Optimal battery settings use the default report settings and with dynamic reporting mode enabled. PIR motion
detection is assumed to be very frequent during active hours and very infrequent during inactive hours.
2
The sensor provides light intensity measurements, but they are not calibrated in lux. See the Technical Reference
Manual for more details [3].
3
No data available from manufacturer on performance outside the range of 15°C to 35°C and 0% to 80% RH.