Datasheet

Subject to alterations and errors
Release 11/03
Trigger 2 to 20mA DC
Checkback signal of the switch setting ‚AUTO‘
1 change over contact
Width 17.5mm
Installation design
Technical data
1. Functions
AUTO output according to input YR
0 permanently OFF
HAND permanently ON
2. Indicators
Green LED ON: indication of supply voltage
Yellow LED ON/OFF: indication of relay output
3. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: any
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
4. Input circuit
Supply voltage: 24V AC/DC terminals A1(+)-A2
Tolerance: 24V AC/DC -15% to +10%
Rated frequency: 48 to 63Hz
Rated consumption: 24V AC/DC 0.4VA (0.4W)
Duration of operation: 100%
Reset time: -
Residual ripple for DC: 10%
Drop-out voltage: >30% of supply voltage
5. Output circuit
1 potential free change over contact
Switching capacity (distance < 5mm): 1250VA (5A / 250V AC)
Switching capacity (distance > 5mm): 2000VA (8A / 250V AC)
Fusing: 8A fast acting
Mechanical life: 20 x 10
6
operations
Electrical Life: 2 x 10
5
operations
at 1000VA resistive load
Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
according to IEC 947-5-1)
Insulation voltage: 250V AC (according to IEC 664-1)
Surge voltage: 4kV, overvoltage category III
(according to IEC 664-1)
6. Measuring circuit
Input: 20mA DC terminals YR(+)-A2
Input resistance: 500
Switching threshold: 2 to 20mA DC
Hysteresis: xed, approx. 10%
7. Checkback
Setting ‚AUTO‘: terminals B1-B2
Maximum switching capacity: 56VA (2A / 28V AC/DC)
Minimum switching capacity: 5mVA (1mA / 5V AC/DC)
Contact resistance: max. 20m
Electrical life: 3 x 10
4
operations at maximum load
8. Accuracy
Base accuracy: ±5% (of maximum scale value)
Adjustment accuracy: ±10% (of maximum scale value)
Repetition accuracy: -
Voltage in uence: -
Temperature in uence: 0.01% / °C
9. Ambient conditions
Ambient temperature: -25 to +55°C (according to IEC 68-1)
Storage temperature: -25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity: 15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree: 2, if built-in 3
(according to IEC 664-1)
OCL1
5.01-5
Coupling modules - OCTO series
5

Summary of content (2 pages)