Datasheet

MONITORING RELAY / 1-PHASE CURRENT
V4IM100AL20
Art.Nr.: 2104400
V4IM100AL20P
Art.Nr.: 2104410
Page 1 of 8
TECHNICAL DATA
SUPPLY CIRCUIT
Terminals A1-A2
Supply voltage 24 ... 240 V AC/DC
Supply voltage tolerance
AC
-15 / +10 %
DC
-30 / +30 %
Rated frequency 16,6 ... 400 Hz or DC
Rated frequency tolerance 16,0 ... 420 Hz
Rated consumption
230 V AC
typ. 0,5 W / 0,9 VA
24 V DC
typ. 0,4 W / 0,45 VA
Duty-cycle 100 %
Backup power time < 20 ms
Recovery time > 500 ms
Drop-out voltage ≥ 6 V
MEASURING CIRCUIT
Terminals Built-in current transformer
Measurand current 1-phase
Measuring method True RMS
Monitoring functions undercurrent (U), overcurrent (O), window (W), under- and over-
current with seperate relay outputs (MM); fault latch selectable
(+L)
Measuring range 100 A AC/DC
Frequency
sinus
16,6 ... 400 Hz
non-sinusoidal
values
50 / 60 Hz (arbitrary waveform)
AC/DC current monitoring
Multifunction
Supply voltage 24-240 V AC/DC
Built-in current transformer
2 change-over contacts
Width 45 mm
Control elements
Start-up suppression
Maximum threshold
Minimum threshold
Function selector
Tripping delay
Status indication
LED U/t: Supply voltage
LED Max: Overcurrent
LED Min: Undercurrent
LED Rel1: Relay status Rel1
LED Rel2: Relay status Rel2
http://tele-online.com
VEO