Datasheet

Subject to alterations and errors
Release 11/02
Coupling relays - OCTO series
Installation design
Width 17.5mm
Analog data encoder 0 to 10VDC
Checkback signal of the switch setting ‚AUTO‘
Technical data
1. Functions
AUTO output according to input YR
0 permanently OFF
HAND output according to set value (regulator)
2. Indicators
Yellow LED ON/OFF: intensity according to the value of the
output signal
3. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: any
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Initial torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
4. Input circuit
Supply voltage: 24V AC/DC terminals A1(+)-A2
Tolerance: 24V AC/DC -15% to +10%
Rated frequency: 48 to 63Hz
Rated consumption: 24V AC/DC 0.58VA (0.33W)
Duration of operation: 100%
Reset time: -
Residual ripple for DC: 10%
Drop-out voltage: >30% of supply voltage
5. Output circuit
Output signal (terminals Y-GND):
Switch setting AUTO corresponding to input signal at
terminals YR - GND
Switch setting 0 0V
Switch setting HAND 0 to 10V
Output capacity Y: 10mW at 10V
(switch setting HAND)
Insulation voltage: 24V AC (according to IEC 664-1)
Surge voltage: 800V, overvoltage category III
(according to IEC 664-1)
6. Checkback
Setting ‚AUTO‘: terminals B1-B2
Maximum switching capacity: 56VA (2A / 28V AC/DC)
Minimum switching capacity: 5mVA (1mA / 5V AC/DC)
Contact resistance: max. 20m
Electrical life: 3 x 10
4
operations at maximum load
7. Accuracy
Base accuracy: ±1% (of maximum scale value)
Adjustment accuracy: ±10% (of maximum scale value)
Repetition accuracy: -
Voltage inuence: -
Temperature inuence: 0.01% / °C
8. Ambient conditions
Ambient temperature: -25 to +55°C (according to IEC 68-1)
Storage temperature: -25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity: 15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree: 2, if built-in 3
(according to IEC 664-1)