® ® CONNECTING THE FUTURE DIGITAL NETWORK INTERFACE PANEL—64 CIRCUITS (DNI-3) USER MANUAL 108469 Issue A Rev 2
Digital Network Interface Panel (DNI-3) User Manual Document Number 108469 Issue A Rev 2 Copyright© Telect, Inc., 1998, All Rights Reserved. Telect and Connecting the Future are registered trademarks of Telect, Inc., 1730 N. Madson St., Liberty Lake, Washington 99019. Twist Lok™ is a trademark of Telect, Inc. Telect’s Twist Lok™ jack is protected by U.S. patent 5,209,678. Note: Telect assumes no liability from the application or use of these products.
Contents 1 Descriptions Digital Network Interface Panel .................................................. 1-1 Capabilities ............................................................................ 1-1 Features .................................................................................. 1-1 System-Level Applications.......................................................... 1-2 Main Assemblies.......................................................................... 1-2 Physical Specifications .....
5 Service Owner Maintenance ..................................................................... 5-1 In Case Of Difficulty ................................................................... 5-1 In-Warranty Service ..................................................................... 5-1 Out-Of-Warranty Service............................................................. 5-2 Repacking For Shipment ............................................................. 5-2 iv Telect, Inc.
1 Descriptions DIGITAL NETWORK INTERFACE PANEL Telect’s DNI-3 is a multifunction support panel for DS3 telecommunications networks. It is an accessible and centralized interconnect point between digital cross-connect systems (DCSs) and central office network elements (NEs). The DNI-3 panel serves as a platform for circuit configuration changes, maintenance activities, and troubleshooting procedures.
Descriptions DNI-3 User Manual SYSTEM-LEVEL APPLICATIONS This illustration shows a DNI-3 within a typical telecommunications network.
2 Installation INSTALLATION CONSIDERATIONS Location and Space The DNI-3 panel mounts flush into both unequal-flange and equal-flange (EIA or WECO) 23" (58.4 cm) network bays. The primary limiting factor of a DNI-3 rack configuration is the number of cables a network bay can accommodate. (The DNI can accommodate 1280 coax cables.) NOTE Telect recommends a maximum of 14 DNI-3 panels per bay, regardless of bay capacity, for easy access and adequate room for cable routing.
Installation DNI-3 User Manual Total Cables Cable Space Needed per Side of Bay (in.2) EIA Bay Spaces Required 13 1664 21.30 39 DCS Terminations Panels 385–416 417–448 14 1792 22.94 42 449–480 15 1920 24.58 45 481–512 16 2048 26.21 48 513–544 17 2176 27.85 51 545–576 18 2304 29.49 54 577–608 19 2432 31.13 57 609–640 20 2560 32.77 60 641–672 21 2688 34.41 63 673–704 22 2816 36.04 66 705–736 24 2944 37.68 69 737–768 24 3072 39.
DNI-3 User Manual Installation INSPECTION Compare the contents of the DNI-3 shipping container with the packing list. Call Telect if you are missing anything. NOTE Telect is not liable for shipping damage. If the shipping container is damaged, keep it for the carrier’s inspection. Notify the carrier and call Telect’s Customer Service Department: 1-800-551-4567 or 1-509-926-6000 Keep the container until you have checked equipment operation.
Installation DNI-3 User Manual 7. Starting at the lowest DNI-3 panel and working upward, connect the DCS OUT cables to the NE-1 OUT termination points on the rear of the DNI-3 panels. 8. Secure the DCS OUT cables to the wire management tray via the tie-down slots. 9. Route the NE IN cables to the same side of the network bay as the DCS IN cables. Tie-wrap the cables in place within the extender panel cable management brackets. 10.
3 Electrical Operation DATA SIGNALS The DCS circuit cables terminate at the lower pair of termination points on the rear of the DNI-3 panel, labeled NE-1. The OUT cable connects to the upper NE-1 termination point and the IN cable connects to the lower NE-1 termination point. The NE circuit cables terminate at the upper pair of termination points on the rear of the DNI-3 panel, labeled NE-2.
Electrical Operation DNI-3 User Manual Inserting a Mini-WECO patch cord into the upper monitor Twist Lok Jack (TLJ) on the front of the DNI-3 panel accesses the NE circuit. Inserting a Mini-WECO patch cord into the lower monitor TLJ on the front of the DNI-3 panel accesses the DCS circuit. 3-2 Telect, Inc.
4 User Functions IN-SERVICE PATCHING To temporarily connect an NE or DCS circuit to an alternate DCS or NE circuit on the same or a different DNI-3 panel or DSX without disrupting service, follow the steps below, using the Twist Lok Jacks (TLJs) on the front of the appropriate DNI-3 panels and the following additional equipment: • • • Four Mini-WECO patch cords (Mini-WECO plug at each end) Two 75-ohm Mini-WECO terminating plugs One dual bridging office repeater (BOR), or two single BORs Step Action 1.
User Functions DNI-3 User Manual 4. Using a fourth Mini-WECO patch cord: a. Insert the plug of one end into BOR position 2, OUTPUT. b. Insert the plug of the other end into the IN TLJ at the first location. 5. Insert a Mini-WECO terminating plug into the OUT TLJ at the first location. 6. Insert a second Mini-WECO terminating plug into the OUT TLJ at the second location.
DNI-3 User Manual User Functions Step Action 1. Using one Mini-WECO patch cord: a. Insert the plug of one end into the IN TLJ at the first location. b. Insert the plug of the other end into the OUT TLJ at the second location. 2. Using a second Mini-WECO patch cord: a. Insert the plug of one end into the OUT TLJ at the first location. b. Insert the plug of the other end into the IN TLJ at the second location.
User Functions DNI-3 User Manual Step Action 1. To monitor the NE circuit outputs, insert a Mini-WECO patch cord into the NE (upper) Monitor TLJ. To monitor the DCS circuit outputs, insert a Mini-WECO patch cord into the DCS (lower) Monitor TLJ. 2. 4-4 Telect, Inc. Connect the other end of the the patch cord to the test set to complete your connection and perform monitoring.
5 Service OWNER MAINTENANCE Telect’s DNI-3 does not need preventive maintenance. IN CASE OF DIFFICULTY If problems occur after initial installation, check all cable connections and the installation instructions in Section 2. IN-WARRANTY SERVICE Contact your Telect equipment distributor, or call a Telect Customer Service Representative: 1-800-551-4567 1-509-926-6000 Telect will repair or replace defective products within the limits of the warranty. See “Repacking for Shipment” in this section.
Service DNI-3 User Manual OUT-OF-WARRANTY SERVICE The procedure for out-of-warranty service is the same as for in-warranty service, except that Telect charges a processing fee, and you must submit a Purchase Order along with a Return Material Authorization (RMA) before returning equipment. Call a Customer Service Representative for help getting these forms. The processing fee guarantees a repair estimate and is credited against actual material and labor costs. REPACKING FOR SHIPMENT Step Action 1.