User's Manual

6.70.104 SS2000 / SS2200 Association Procedures 5/2010
Confidential – Information contained in this document is considered proprietary and confidential, and is intended for the internal
use of Telkonet, Inc. our contracted Partners and VARs, and customers. This content is protected by all applicable copyright
restrictions. © 2010 Telkonet, Inc. 2
Overview
This document describes the process to associate (i.e. link) an SS2000 / SS2200 to either an
SS1107 or SS5000 / SS5200. The document is separated by base-station type (SS1107 and
SS5000 / SS5200).
Terminology:
“Controller” – The SS1107 PTAC Controller unit
“Sensor” – The SS2000 / SS2200 Occupancy Sensor
“Poke” – the process of inserting the Smart Tool into the pinhole on a specified unit, and
depressing the microswitch within for a period of approximately ¼ second (unless
another hold time is specified).
“Smart Tool” – An unfolded paper clip or similar long, rigid wire
Preparation:
Ensure the components are installed per Telkonet Recommended Best Practices. In particular:
Controller should be solidly-affixed to the wall and/or outlet
Controller antenna should be extended, and not bunched-up inside the unit housing or
wall
Sensor should be temporarily located in its desired location via double-sided tape (if radio
link to the Controller)
Sensor should be firmly mounted to its desired location with all low-voltage wiring in place
(if using hard-wired link and power from the Controller)
Procedures: SS2000 to SS1107 Controller
Step One – Power the Controller
1. Apply Power to the unit
2. Poke the Controller
3. The LED in the unit will begin a double flash (blink-blink-pause). This indicates that
the Controller is in sensor acquisition mode. Observe the rate of the blinking (for
comparison in step two)
Step Two – Initiate the Association
1. Poke the sensor
2. Observe the LED on the controller. The LED should continue a double-blink, but the
speed of the blink will double as well.