EcoWave Installation Guide PST6000 and PST6550
Table of Contents Table of Contents ................................................................................................................... 1 Installation Requirements.......................................................................................................... 2 Required Equipment ............................................................................................................. 2 Hardware ....................................................................................
Installation Requirements Required Equipment Hardware • • • • • • • • • • EcoAir (P/N: PST6550) EcoInsight/EcoSource (P/N: PST6000) Voltmeter Small Phillips screwdriver Wire nut or electrical tape Wire stripper Wire cutter Security screw wrench Level Two AA Batteries Regulatory Compliance This device complies with Part 15 of the FCC Rules.
Wiring the EcoInsight/EcoSource 1. Locate the wiring in the HVAC Unit. 2. Review the table below and determine where the EcoInsight/EcoSource will be mounted. Mounting Consideration RF Interference 3. 4. 5. 6. Best Practice If the EcoInsight/EcoSource will be mounted inside a metal HVAC unit or in a room with a large amount of metallic equipment, an external antenna may be necessary. Turn the power off at the circuit breaker. Lockout and label all circuits in accordance with local code.
16. Refer to either the wiring diagram provided by your Telkonet Project Manager for this install or use the wiring pinouts below in Figure 1and Table 1.
17. Starting at the bottom of the terminal block and working up, use a Phillips screwdriver to secure each of the HVAC wires into the appropriate pins on the terminal block. See Figure 2. Figure 2: Connecting Wiring from Bottom to Top 18. If any wires are left unused, cap off the wire using a wire nut or electrical tape. 19. Verify each wire is secure by gently tugging on it. 20. Verify the completed wiring looks similar to Figure 3. Figure 3: EcoInsight/EcoSource Backplate Wired to HVAC Unit 21.
Wireless Installation of the EcoAir 1. Review the table below and determine where the EcoAir will be mounted. Mounting Consideration Temperature Best Practice The EcoAir should be mounted on a wall away from heat or cold sources that could affect its temperature reading. This includes outside-facing walls with poor insulation, walls with pipes circulating hot water, and walls near radiators. If a suitable location without a heat or cold source is not available, contact a Telkonet Project Manager.
Configuration Join the EcoInsight/EcoSource to the EcoConnect Enter the join codes on each device. The PAN and Channel will be set automatically. Required Equipment Hardware • An EcoCommander or EcoCommander Pro • An EcoConnect • An EcoInsight/EcoSource that has been wired • Unbent paperclip or pen Join Process 1. 2. 3. 4. 5. Verify the EcoCommander or EcoCommander Pro is powered. Verify the EcoConnect is powered. Verify the EcoConnect is connected to the EcoCommander or EcoCommander Pro.
Figure 5: EcoSource and Join Code 9. 10. 11. 12. 13. Verify the LED on the front of the EcoSource blinks a “Red, Red, Green” sequence. Wait 60 seconds for the EcoSource to find the network. Verify that the EcoSource reboots. Verify that the LED on the front of the EcoSource is lit solid green. Continue to Step 18. Use figure 6 to enter the join code on the EcoInsight. Figure 6: EcoInsight and Join Code 14. Verify the two horizontal bars appear above "Room Temp".
18. Using the paperclip or pen, press the pushbutton on the front of the EcoConnect once. The LED on the front of the EcoConnect should change from blinking green to solid green. This means the EcoConnect will no longer accept join requests from ZigBee devices. 19. If configuring a multi-bind system where multiple EcoInsights/EcoSources will be used to control one or more HVAC units, repeat steps 1 through 18 for each EcoInsight/EcoSource. 20.
EcoAir to EcoInsight/EcoSource Association Associating One EcoAir with One EcoInsight/EcoSource (Standard) In most installations, one EcoAir will be associated with one EcoInsight/EcoSource. The EcoInsight/EcoSource manages Recovery Time calculations, temperature profiles, and HVAC drift and drive. The EcoAir acts as a remote control to change settings on the EcoInsight/EcoSource. Required Equipment • Paperclip or pen Associate the EcoAir with the EcoInsight/EcoSource 1.
Figure 9: Maintenance → Learn Menu With 1 Device Associated, In Learn Mode 9. Hold the “On / Off” button on the EcoAir until the EcoAir displays two digits on its screen. This may take up to 10 seconds. The displayed digits will be the last two digits of the EcoInsight’s serial number. 10. Verify the larger number in the EcoInsight “Learn” menu has increased by one. 11. Press the Fan button on the EcoInsight twice to exit the Maintenance Menu. Association is complete. Continue to Step 12.
Associating One EcoAir with Multiple EcoInsights/EcoSources (Multi-Bind) In some installations, one EcoAir may communicate with multiple EcoInsights/EcoSources. One EcoInsight/EcoSource, designated the Master EcoInsight/EcoSource, manages the Recovery Time calculations and temperature profiles. All other EcoInsights/EcoSources, designated Slave EcoInsights/EcoSources, drift or drive their own HVAC unit at the command of the Master EcoInsight/EcoSource.
23. If your device is an EcoSource, continue to the next step. If your device is an EcoInsight, continue to Step 30. 24. Locate the recessed push button above the LED on the Slave EcoSource. 25. Using the paperclip or pen, press the push button three times. The Slave EcoSource LED will doubleblink red. 26. Hold the “On / Off” button on the EcoAir until the EcoAir displays two digits on its screen. This may take up to 10 seconds.
Troubleshooting Issues Configuring Firmware Problem Potential Cause Potential Solution The EcoInsight/EcoSource says cmd not found after entering a zb command. Backspace was used while typing the zb command. Re-enter the zb command without using backspace. The channel was not set to the value I entered. The channel you entered was below 11 or above 26. Re-enter the zb command. Recommended channels are 15, 20, 25, and 26. Backspace was used while typing the zb command.