User's Manual

EcoWave
Installation
Guide
Telkonet,
Configuration
10200 W. Innovation Dr., Ste. 300
Revision 9
Milwaukee
, WI 53226
Page
13
(800) 380
-
9640
www.telkonet.com
23. If your device is an EcoSource, continue to the next step. If your device is an EcoInsight, continue to
Step 30.
24. Locate the recessed push button above the LED on the Slave EcoSource.
25. Using the paperclip or pen, press the push button three times. The Slave EcoSource LED will double-
blink red.
26. Hold the “On / Off” button on the EcoAir until the EcoAir displays two digits on its screen. This may
take up to 10 seconds. The displayed digits will be the last two digits of the EcoSource’s serial number.
27. Verify the Slave EcoSource LED has changed from double-blinking red to blinking green.
28. Remove power from the Slave EcoSource.
29. Repeat steps 19 through 28 for each Slave EcoInsight/EcoSource. Then continue to Step 30.
30. Press and hold the “Fan” button on the Slave EcoInsight for 10 seconds, then press the “On/Off”
button. The Maintenance Menu should appear. Verify the text “Learn” appears in the Maintenance
Menu.
31. Press the “On/Off” button to enter the Learn menu. Either one or two numbers will appear in the
center of the screen, depending on the number of devices associated with the Slave EcoInsight. See
Figure 7 and Figure 8.
32. Assign a unique installer number by pushing the up or down arrows. The smaller number on the screen
will increase or decrease.
33. Press the “On/Off” button again to activate Learn Mode. The text “On” should appear next to the
smaller number. See Figure 9.
34. Hold the “On / Off” button on the EcoAir until the EcoAir displays two digits on its screen. This may
take up to 10 seconds. The displayed digits will be the last two digits of the EcoInsight’s serial number.
35. Verify the larger number in the Slave EcoInsight “Learn” menu has increased by one. Press the Fan
button on the EcoInsight twice to exit out of the Maintenance Menu.
36. Remove power from the Slave EcoInsight.
37. Repeat Steps 19 through 22 and Steps 30 to 36 for each Slave EcoInsight/EcoSource. Then continue to
Step 38.
Power Up All Devices In Order
38. Remove the two AA batteries from the EcoAir.
39. Return power to the Master EcoInsight/EcoSource.
40. Insert the two AA batteries back into the EcoAir.
41. Return power to each Slave EcoInsight/EcoSource, one at a time.
Verify the Association
42. Activate heat mode on the EcoAir (exact steps will vary by EcoAir firmware).
43. Increase the set temperature above the current room temperature.
44. Verify both the Master EcoInsight/EcoSource and the Slave EcoInsight/EcoSource engage their HVAC
unit’s heating mode.
45. Activate cool mode on the EcoAir (exact steps will vary by EcoAir firmware).
46. Decrease the set temperature below the current room temperature.
47. Verify both the Master EcoInsight/EcoSource and the Slave EcoInsight/EcoSource engage their HVAC
unit’s cooling mode.
48. Change the fan speed on the EcoAir to high by pressing the “Fan” button until the High fan speed is
indicated.
49. Verify both the Master EcoInsight/EcoSource and the Slave EcoInsight/EcoSource engage their HVAC
unit’s fan at the highest speed.
50. Configuration is complete.