User's Manual

EcoSource High Voltage Installation
approved electrical connection inside the junction box. If a site-specific wiring diagram was
provided, refer to this for wiring. If no diagram was provided, refer to Figure 7.
. (If controlling proportional valve or ECM fan, see Appendix A.) Any unused wires must be capped according
to NEC standards.
1
For variable output connections, see Appendix A on page 39.
Figure 7: Wiring
1
The High Voltage backplate comes with R, Switched Power 1 and Switched Power 2 jumped together with a Red Wire nut. These can be
connected to the same power source assuming all controlled Fans and Valves will be controlled at the same voltage that will be powering
the thermostat. If a different voltage will be used for any of the Controlled elements of the HVAC then the appropriate power source
should be connected to the Switched Power 1 (W1,Y1) and Switched Power 2 (G,O,W2) ter minals .