EcoSource High Voltage Installation
Table 1-Wiring:
Pin Label on Backplate Function
1 R (Power) 12-277VAC power from HVAC, used to power the thermostat
2 C (Common) AC Common
3 AUX (Auxiliary) User defined
4 W1 (Heat) (Strip) Heat call or strip heat call (depends on programming)
5 Switched Power 1 (W1/Y1) Provides alternate power for W1 and Y1
6 Y1 (Cool) (Comp) Cool/Compressor call
7 G (Fan) Fan Call - Low speed
8 O (B) (G2) (Y2) (Changeover)
Multi-use - depends on programming and site requirements:
Changeover
2
nd
Stage Fan
2
nd
Stage Cooling
9
Switched Power 2
Provides alternate power for G, O, and W2
10
W2 (Y2) (G2) (G3) (Multi-speed)
Multi-use - depends on programming and site requirements:
2
nd
stage heat
Electric heat (for HPs with strip heat, etc.)
Emergency heat
Step 14 Carefully push the wired connections back into the JBOX.
Step 15 Mount pre-wired 16 gauge SS6000 backplate on top of JBOX adapter, using four #5 ½” coarse
thread screws. See Figure 8.
Figure 8: Backplate on Adapter Plate
Step 16 Ensure no airflow from JBOX or wall cavity is able to seep into the thermostat through the wire
harness. Telkonet recommends the use of UL caulk or UL rated insulating tape as shown in
Figure 9 to avoid false temperature readings.
EcoWave Featuring EcoTouch IO&M Guide Telkonet, Inc.