Proportional Valve Control
Applies only to the SS6000-VO model of thermostat
Figure 31-Before Connecting
Figure 32-After Connecting
Connecting Pins
Controlling the Cooling Valve with a 0-10 Volt Signal
1. Using the J5 Molex connector, connect Pin 5 to the Valve 0-10v input line.
2. Connect pin 1 (GND) to the Common line on the valve.
Note: You must also jumper pin 1 to the 24v COMM if the valve is referencing 24v Common.
Controlling Heating Valve with a 0-10 Volt Signal
1. Using the J5 Molex connector, connect Pin 6 to the Valve 0-10v input line.
2. Connect pin 1 (GND) to the Common line on the valve.
Note: You must also jumper pin 1 to the 24v COMM if the valve is referencing 24v Common.
Controlling an ECM Fan Motor
(Firmware must be pre-setup to provide this output.)
Using the J5 Molex connector, connect Pin 6 to the ECM Motor 0-10v input line.
Connect pin 1 (GND) to the Common line on the ECM Motor control board.
Note: You must also connect the 24v COMM if the valve is referencing 24v Common.
Adding Jumpers
Place 2 jumpers side-by side on connector J6. (J6 is located below the radio board. See Figure 31.
Place one jumper on pins 1 -> 2, as shown in Figure 32. Jumper 1->2 is for 0-10V; no jumper 4-20mA.
Place the other jumper on pins 3 -> 4. Jumper 3->4 is for 0-10V; no Jumper 4-20mA.