User Manual

Operational Checkout and System Commissioning
167
System Will Not Power Up
Step
Yes
Go to
step
No
Go to step
1. Using a DVM, check the DC Voltage level on the high current
barrier strip. Is it 12 VDC ±1.5 VDC?
13 12
2. Verify that the high-current ON/OFF switch is in the ON
position.
4 3
3. Place high-current ON/OFF switch is in the ON position.
- -
4. Test the battery. Is it fully charged and operational?
6 5
5. Replace the battery.
End End
6. Verify that the battery terminals are clean and that the
connectors themselves are free of corrosion and properly
torqued.
8 7
7. Disconnect battery, and disconnect positive and negative wire
from high current barrier strip.
- -
8. Using a DVM, check for continuity.
10 9
9. Repair or replace wiring as indicated.
End End
10. Repair the Distribution Barrier Strip.
End End