User Guide
6 Using the product 
 11 
6  Using the product 
6.1.  Performing settings 
Setting the sensitivity 
There are two sensitivity levels: HI (high, default) and LO (low). 
The LO level is 8x less sensitive than the HI setting. At high 
refrigerant gas concentrations, set the sensitivity to LO. 
> Press [ ] briefly to set the sensitivity to LO. 
> Press [ ] again to revert to the HI level. 
6.2.  Finding leaks 
NOTICE 
Sensor destruction due to desorbing substances (e.g. oils)! 
>  Do not operate the instrument in contaminated environments. 
1.  Move the leakage detector to the site where the leak is 
suspected. 
Leak detection can only be carried out correctly if the probe 
is guided directly over the leak. 
2.  Guide the probe head over the surface to be tested at a 
maximum distance of 6 mm and a rate of 2.5 to 5 cm per 
second. 
-  If the instrument detects a leak, the yellow gas concentration 
indicator LEDs light up and the instrument starts to beep 
rapidly. The larger the leak, the more segments light up. 
3.  Move instrument away from the leak briefly. 
>  In the case of high refrigerant concentrations: before going back 
to the leak, set the sensitivity to LO. 
4.  Guide the probe head back to the leak in order to precisely 
locate the site. 
> Set the sensitivity back to HI as soon as the leak has been 
precisely located. 