Datasheet
UDG-11118
UVLO
R
ON2
R
ON1
V
IN
+
TPS40322
VIN_OK
15 mA
= m ´
ON1
VIN _ HYS 15 A R
( )
æ ö
+
= ´
ç ÷
ç ÷
è ø
ON1 ON2
ON2
R R
VIN _ UVLO 1.24 V
R
TPS40322
www.ti.com
SLUSAF8D –JUNE 2011–REVISED JANUARY 2014
Overvoltage and Undervoltage Fault Protection
The TPS40322 has output overvoltage protection and undervoltage protection capability. The comparators that
regulate the overvoltage and undervoltage conditions use the FBx pin as the output sensing point so the filtering
effect of the compensation network connected from COMPx to FBx has an effect on the speed of detection. As
the output voltage rises or falls below the nominal value, the error amplifier attempts to force FBx to match its
reference voltage. When the error amplifier is no longer able to do this, the FB pin begins to drift and trip the
overvoltage threshold (V
OVP
) or the undervoltage threshold (V
UVP
) as described in the ELECTRICAL
CHARACTERISTICS table.
When an undervoltage fault is detected, the TPS40322 enters hiccup mode and resumes normal operation when
the fault is cleared.
When an overvoltage fault is detected, the TPS40322 turns off the high-side MOSFET and latches on the low-
side MOSFET to discharge the output current to the regulation level (within the power good window).
When operating in dual-channel mode, both channels have identical but independent protection schemes which
means one channel would not be affected when the other channel is in fault mode.
When operating in two-phase mode, only the FB1 pin is detected for overvoltage and undervoltage fault.
Therefore both channels take action together during a fault.
Input Undervoltage Lockout (UVLO)
A dedicated UVLO pin allows the user to program the desired input turn-on threshold voltage. The diagram is
shown in Figure 22. The desired input turn-on threshold can be calculated using Equation 6. The input turn off
hysteresis can be calculated using Equation 7.
(6)
(7)
Figure 22. Input UVLO Diagram
Power Good
The TPS40322 provides an indication that output is good for each channel. This is an open-drain signal that pulls
low when any condition exists that would indicate that the output of the supply might be out of regulation. These
conditions include:
• Feedback voltage (V
FB
) is more than ±12.5% from nominal
• Soft-start is active
Thermal Shutdown
If the junction temperature of the device reaches the thermal shutdown limit of 150°C, the PWMs and the
oscillators are turned off and HDRVs and LDRVs are driven low. When the junction cools to the required level
(130°C typical), the PWM initiates soft start as during a normal power-up cycle.
Copyright © 2011–2014, Texas Instruments Incorporated Submit Documentation Feedback 19










