Manual
Immersion
heater timer
IHT/T   (GPT/T)
IHT/W  (GPT/W)
A GE Power Controls Company
Grässlin UK
Vale Rise
GB-Tonbridge/Kent TN9 1TB
Tel  (0
 17 32) 35 98 88
Fax (0
 17 32) 35 44 45
www.tfc-group.co.uk
Installation - General Notes
1. Installation should be carried out in accordance  
  with the current edition of the I.E.E. Wiring  
  Regulations. It is recommended that installation is 
  undertaken only by a qualified electrician.
2. The timer should not be mounted on an unearthed  
  metal or metallised surface.
3. If the timer is to be connected to an appliance that is 
  required to be earthed the supply earthing conductor  
  and the appliance earthing conductor should be 
  terminated together in the earth terminal provided  
  within the timer.
4. It must be ensured that the brass inter-connecting
  link is correctly positioned and retained in the 
  terminals during connection of the supply conductors 
  (applicable to types IHT/T and IHT/W).
5. When cutting out the required apertures in the cover  
  to accommodate the input and output cables/cords it  
  should be ensured that no sharp edges remain. 
6. All terminals are suitable for fixed cables, and for
  flexible cables or cords.
7. For stranded wires use ferrules supplied.
Installation Procedure
1. Switch the supply off at the mains. Means of dis-
  connection from the supply having at least 3mm 
  contact separation in all poles must be incorporated  
  in the fixed wiring mains supply. 
2. Loosen screws (a) and separate housing from timer 
  base. Pull timeswitch module off backplate. Offer 
  backplate to mounting location and mark fixing 
  points b, c and d. Drill wall for screw fixings. Fix 
  backplate to wall. Push timeswitch module onto 
  backplate, ensuring  good engagement of tab 
  terminals with receptacles.
3. Bare wires for 6mm (1/4 inch) maximum; insert into  
  terminals and secure with the screws, in accordance  
  with circuit diagram label beneath terminals. 
4. Secure cables/cords with clamp provided and check 
  all wiring (see figure 4). Note: Mains supply using 
  fixed wiring does not need to pass through clamp. 
5. Cut out cable entries on underside of housing as 
  necessary to accomodate cables/cords. Please refer 
  to 5. above. 
6. Refit housing to timer base. 
7. Switch on mains. 
Installation as general purpose timer
If you are not controlling an immersion heater, but 
you are still controlling a mains-fed load, please wire 
in accordance with “Immersion Heater Connections” 
diagram shown in this instruction. If the timer is supplied 
by the mains, but you wish to control a circuit which 
must be kept electrically separate to the incoming mains 
supply, please follow the instructions below. 
Removal of the “bridge wire” between terminals 2 and 
3 enables the timer to be used as a general purpose 
timer, since the switch is then electrically separate from 
the mains input to the motor. The switch can then be 
used to control a separate circuit. When installing as 
a general purpose timer, follow instructions 1. and 2. 
above, then slacken screws to terminals 2 and 3 and 
remove bridge wire; affix general purpose timer wiring 
diagram provided over existing IHT wiring label; wire in 
accordance with general purpose diagram, then follow 
instructions 4. to 7. above. 
Setting up
Rotate minute hand until arrowhead on clock face, 
aligns with correct time on outer dial. i. e. 8=8.00 
a.m., 18=6.00 p.m. (see figure 1). When setting up 
seven day version (IHT/W, GPT/W), align correct time 
on outer dial, within current day sector of dial. 
Note: Weekdays are printed on dial in abbreviations of 
three languages.
Twenty-four hour (IHT/T, GPT/T) minimum switching 
time: 15 minutes. 
Seven day (IHT/W, GPT/W) minimum switching time: 
2 hours. 
To set ON/OFF times, move all tappets between 
ON and OFF times required to outer position i.e. to 
set ON at 8.00 a.m. and OFF at 11.00 a.m. move all 
tappets to outer position (see figure 2): Set any other 
ON/OFF times in a similar manner. 


