If the improvement is less than 5% then it is normally nor worth spending the expense on cleaning
•
The above verification should only be carried out when the insolation is effectively constant (clear sky,
strong sunshine, no clouds)
•
The back surface of the module normally does not need to be cleaned but, in the event this is deemed
necessary, avoid the use of any sharp projects that might damage the penetrating the substrate
material.
• Cover the front sur
face of modules by an opaque material when repairing. Modules when exposed to
sunlight generate high voltage and are dangerous.
•
Trina Solar PV modules are equipped with bypass diodes in the junction box. This minimizes module
heating and current losses.
Do not try to open the junction box to change the diodes even if they malfunction.
In a system using a battery, blocking diodes are typically placed between the battery and the PV
module output to prevent battery discharge at night.
• Product Replacement:
In the event that a module is damaged (broken glass or scratch on back sheet) and needs to be replaced
then
Observe the safety precautions listed earlier in the manual
Wear cut resistant gloves and other personal protective equipment required for the parti
installation.
Isolate the impacted array string to prevent current flow before attempting to remove the module.
Disconnect the connectors of the affected module using the related disconnect tool provided by
suppliers.
Replace the damaged module with
Check the open circuit voltage of the array string and verify that this is within 10V of the other
strings to be connected in parallel.
Turn the isolator back on.
• Troubleshooting:
If your installation does not work
•
Reporting Technical Issues or Claims:
Contact your installer
Contact Trina Solar after sales service team at
Submit the Customer Feedback form at:
service representatives will contact you within 5 business days. A username and password is
required to send feedback from the customer service link
For module specifications or datasheets, please download from:
9. WARNING
WARNING: For any electrical maintenance, the PV system must first be shut down. Improper maintenance
can cause lethal electric shock and/or burns.
SP-1000
The Solar PaQ
Trina ALLMAX
M Plus 60 Cell 295 watt
UPC: 861150002609
If the improvement is less than 5% then it is normally nor worth spending the expense on cleaning
The above verification should only be carried out when the insolation is effectively constant (clear sky,
The back surface of the module normally does not need to be cleaned but, in the event this is deemed
necessary, avoid the use of any sharp projects that might damage the penetrating the substrate
face of modules by an opaque material when repairing. Modules when exposed to
sunlight generate high voltage and are dangerous.
Trina Solar PV modules are equipped with bypass diodes in the junction box. This minimizes module
Do not try to open the junction box to change the diodes even if they malfunction.
In a system using a battery, blocking diodes are typically placed between the battery and the PV
module output to prevent battery discharge at night.
In the event that a module is damaged (broken glass or scratch on back sheet) and needs to be replaced
Observe the safety precautions listed earlier in the manual
Wear cut resistant gloves and other personal protective equipment required for the parti
Isolate the impacted array string to prevent current flow before attempting to remove the module.
Disconnect the connectors of the affected module using the related disconnect tool provided by
Replace the damaged module with
a new module of the same type.
Check the open circuit voltage of the array string and verify that this is within 10V of the other
strings to be connected in parallel.
If your installation does not work
properly, please inform your installer immediately.
Reporting Technical Issues or Claims:
Contact Trina Solar after sales service team at
http://customerservice.trinasolar.com
Submit the Customer Feedback form at:
http://www.trinasolar.com/
and one of our technical
service representatives will contact you within 5 business days. A username and password is
required to send feedback from the customer service link
For module specifications or datasheets, please download from:
http://www.trinasolar.com/
WARNING: For any electrical maintenance, the PV system must first be shut down. Improper maintenance
can cause lethal electric shock and/or burns.
If the improvement is less than 5% then it is normally nor worth spending the expense on cleaning
The above verification should only be carried out when the insolation is effectively constant (clear sky,
The back surface of the module normally does not need to be cleaned but, in the event this is deemed
necessary, avoid the use of any sharp projects that might damage the penetrating the substrate
face of modules by an opaque material when repairing. Modules when exposed to
Trina Solar PV modules are equipped with bypass diodes in the junction box. This minimizes module
In a system using a battery, blocking diodes are typically placed between the battery and the PV
In the event that a module is damaged (broken glass or scratch on back sheet) and needs to be replaced
Wear cut resistant gloves and other personal protective equipment required for the parti
cular
Isolate the impacted array string to prevent current flow before attempting to remove the module.
Disconnect the connectors of the affected module using the related disconnect tool provided by
Check the open circuit voltage of the array string and verify that this is within 10V of the other
properly, please inform your installer immediately.
http://customerservice.trinasolar.com
and one of our technical
service representatives will contact you within 5 business days. A username and password is
http://www.trinasolar.com/
WARNING: For any electrical maintenance, the PV system must first be shut down. Improper maintenance