Third Party Verification Claim

When a measurement is needed to determine compliance with a clause the actual
measured value must be recorded in the space provided. A simple 'Yes' / 'No'
response is not sufficient. (See 'UL Certification Program - Work
Instructions for Completion of Construction Review Datasheets (CRD) For C-UL
Mark' (00-OP-W0038) for details).
CONSTRUCTION COMPLIANCE REVIEW RECORD
Sample Identification –
Currently certified
product used for
comparison (include
Report references if not
in the same report):
Sader Power Enterprises LLC, SR-3000 Sader RAQ 3-Panel
and SR-1000 Sader RAQ 1-Panel
Alternate
construction
details:
Addition of stainless steel, grade A2 (304SS), star
washers to bond rail joints together. Addition of
bonding wire between panel rail and spacer brace.
Addition of Tyco Solar Lock ground lug. Addition of
304SS grounding hardware
[] No samples received or examined. Drawings or other information was
provided to support the [ alternate construction. ][ revised construction. ]
[ addition of a new model that is similar to a currently certified product. ]
[x] See the following table.
Sample Card
No.
Date
Received
Sample
No. Manufacturer, Product Identification and Ratings
1797176 2014-01-
15
1-6 Sader Power Enterprises LLC, SR-3000 Sader
RAQ 3-Panel
Ground hardware and (KDER.E69905), Tyco model
2058729 shown below