Switch-off time delay «Light»
Set the desired minimum switch-off delay time for the «Light» switching
contact on the potentiometer.
Transfer zones approx. 5min.
Working areas approx. 10min.
The setting corresponds to the minimum value. The effective switch-off de-
lay time varies between the set value and the maximum value of 15 min.
(self-learning effect). When set to 2 min., the switch-off delay is xed.
Brightness threshold «LUX» Scale
Transfer zones (no working area) approx. 2
Working areas (ofces, conference rooms) approx. 4
Activities requiring good visibility (laboratory, drawing) > 5
Deactivation of brightness measurement «on»
Depending on the installation location, natural light intensity, furniture, re-
ection characteristics of the room and the furniture it may be necessary to
correct the settings by 1-2 steps on the scale.
●
●
●
●
●
●