3.3 Communication objects
3.3.1 Object characteristics
Cheops control features 12 communication objects.
Objects 2, 3, 4, 5, 6 and 8 can assume various functions, depending on the configuration
Table 3
No.
Function
Object name
Type
Response
0
Define set point temperature
Basic set point value
2 byte
EIS5
Receive
1
shift set point temperature
Manual shift of set point value
2 byte
EIS5
Send /
Receive
2
Transmit actual value
Actual value
2 byte
EIS5
Send
Input actual value
Receive
3
Pre-selection of operating
mode
Pre-selection of operating
mode
1 byte
KNX
Receive
1 = night, 0 = standby
Night < - > Standby
1 bit
4
Input for presence signal
Presence
1 bit
Send /
receive
1 = comfort
Comfort
1 bit
Receive
5
Input of window state
Window state
1 bit
Send /
receive
1 = frost protection
Frost/heat protection
1 bit
Receive
6
1 = decrease/0 = increase
adjustment of set point
temperature
1 bit
Receive
Calculates maximum
actuating value
maximum actuating value
1 byte
EIS6
Send /
receive
0 .. 100%
Actual valve position
1 byte
EIS6
Send
7
Current actuating value
heating
actuating value heating
1 byte
EIS6
Send
8
Actuating value in cooling
mode
actuating value cooling
1 byte
EIS6
Send
Switching actuating value
Actuating value of additional
heating
1 bit
Send
Continuous actuating value
Actuating value of additional
heating
1 byte
EIS6
Send
9
Transmit
Current set point value
2 byte
EIS5
Send
10
Transmit
Current operating mode
1 byte
KNX
Send
11
Heating/cooling
Switchover
1 bit
Receive