Object 3 "Pre-selection of operating mode" / "Night <-> Standby"
The function of this object depends on the "Objects for determining operating mode"
parameter on the "Operating mode" parameter page.
Table 5
Objects for determining the operating
mode
Function
New: Operating mode, presence
window, window status
With this setting, the object is a 1 byte object. One
of 4 operating modes can be directly activated.
1 = comfort, 2 = standby, 3 = night,
4 = frost protection (heat protection)
The details in brackets relate to the cooling
operation
Old: Comfort, night, frost
With this setting, the object is a 1 bit object. Night
or standby operating mode can be activated.
0=standby 1=night
* If a different value from 1...4 is sent to object 3, then operating mode 1 = comfort is adopted
Object 4 "Presence / comfort"
The function of this object depends on the "Objects for determining operating mode"
parameter on the "Operating mode" parameter page.
Table 6
Objects for determining the operating
mode
Function
New: Opertaing mode, presence
window, window status
The status of a presence indicator (e.g. sensor,
movement indicator) can be received via this object.
A 1 on this object activates the comfort operating
mode.
If a presence indicator is connected to Interface E2,
its status is sent via this object to the bus.
Old: Comfort, night, frost
A 1 on this object activates the comfort operating
mode.
This operating mode takes priority over night and
standby operation.
Comfort operation is deactivated by sending an 0 to
the object.