Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 14 of 71
Object 5 "Window state" / "Frost/heat protection"
The function of this object depends on the "Objects for determining operating mode"
parameter on the "Operating mode" parameter page.
Table 7
Objects for determining the operating
mode
Function
New: Operating mode, presence
window, window status
The status of a window contact can be received via
this object.
A 1 on this object activates the frost / heat
protection operating mode.
If a window contact is connected to Interface E1, its
status is sent via this object to the bus.
Old: Comfort, night, frost
A 1 on this object activates the frost protection
operating mode.
During the cooling operation, the heat protection
mode is activated.
The frost/heat protection operating mode takes top
priority.
The frost/heat protection mode remains until it is
cleared again by a 0.
Object 6 „"adjustment of set point temperature" / "maximum actuating value" /
"Actual valve position"
The function of this object depends on the "Function of Object 6" on the "Device setting"
parameter page.
Table 8
Function of Object 6
Function
Increases / decreases the set point value
This object can increase or decrease the current set
point value in increments.
A 0 on the object results in an increase in the set
point value and is equivalent to pressing the red
button.
A 1 on the object results in a decrease in the set
point value and is equivalent to pressing the blue
button.
The increment is set on the "Operation" parameter
page. The achieved offset can be reported by
Object 1.