Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 15 of 71
Continued:
Function of Object 6
Function
Determine the maximum actuating
value
This object has 2 functions here:
1. Receives actuating values from the other
actuators (other rooms), in order to be able
to compare them with its own.
2. Sends its own actuating value to the heating
boiler, if it is higher than the others.
(See also: Determining maximum actuating
value)
Sends the actual valve position
Sends the current valve position (0..100%).
This function can be enabled (e.g. diagnosis) as and
when required.
This function is not required for normal operation.
Object 7 "Current actuating value, heating"
This object is present only when selected on the "Heating control" page as follows.
The current actuating value (0…100%) can then be sent to other continuous actuators (Cheops
drive) in the same room/control circuit.
If you wish to read out Object 7 via the bus, Object 8 must not be present ("Used control
functions" on the "Settings" parameter page set to "Heating control only"). The
"Read" flag must be set.
If you wish to read out Object 8 via the bus, this parameter must be set to "Not present".
Object 8 "actuating value cooling"/"Actuating value of additional heating"
The function of this object depends on the "Input for actual value" parameter on the "Settings"
parameter page.
Table 9
Used control functions
Function
Heating and cooling
Sends the cooling actuating value to control a
cooling ceiling, fan coil unit etc.
2-step heating with switching additional
step
Sends the switching command to control the
additional step (on/off)
2-step heating with continuous
additional step
Sends the continuous actuating value to control the
additional step (0…100%)