Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 16 of 71
Note:
In the "Heating control" setting, the object is not available because neither the cooling
function nor the additional step are present.
If you wish to read out Object 8 via the bus, Object 7 must be hidden (see above) and the
"Read" flag must be set.
Object 9 "Current set point value"
This object sends the Current set point temperature as a EIS 5 telegram (2 bytes) on the bus.
The send response can be set on the "Heating control" parameter page.
Object 10 "Current operating mode"
This object sends the current operating mode as a 1 byte value.
The send response can be set on the "Operating mode" parameter page.
The operating modes are coded as follows:
Table 10
Value
Operating mode
1
Comfort
2
Standby
3
Night
4
Frost protection/heat
protection
Object 11 "Switchover"
This object is available if an automatic switching between heating and cooling is not required.
The setting is made on the "Cooling control" parameter page
The cooling operation is forced via a 1 and the heating operation via a 0.