Operation Manual
Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 19 of 71
3.4.2 Set point values
Table 12
Designation
Values
Meaning
Basic set point value after
download of application
18 °C, 19 °C, 20 °C,
21 °C, 22 °C, 23 °C,
24 °C, 25 °C
Output set point value for the
temperature control.
Reduction in standby
operating mode at heating
0,5 K, 1 K, 1,5 K
2 K, 2.5 K, 3 K
3,5 K, 4 K
Example: with a basic set
point value of 21
o
and a
2K reduction in heating
operation, Cheops control
controls at a set point value of
21 – 2 = 19°C
Reduction in night operating
mode at heating
3 K, 4 K, 5 K
6 K, 7 K, 8 K
By what value should the
temperature be reduced in
night mode?
Set point value for frost
protection mode
3 °C, 4 °C, 5 °C
6°C, 7 °C, 8 °C
9 °C, 10 °C
Preset temperature for frost
protection operation in
heating mode
(Heat protection operation
applies in cooling mode).
Transmission of current set
point values
No cyclical transmission
Every 2 min
Every 3 min
Every 5 min
Every 10 min
Every 15 min
Every 20 min
Every 30 min
Every 45 min
Every 60 min
How often should the
currently valid Set point value
be sent?
Send only at a change.
Send cyclically