Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 27 of 71
Continued:
Designation
Values
Meaning
Integral time of the cooling
controller
Pure P control
30 min, 45 min, 60 min
75 min, 90 min, 105 min
120 min, 135 min, 150 min
165 min, 180 min, 195 min
210 min, 225 min
see Appendix
Temperature control
For PI control only:
The integrated time
determines the reaction time
of the control.
These times can be adapted to
suit particular circumstances.
If the cooling system is over-
dimensioned and therefore too
fast, shorter values should be
used. Conversely, under-
dimensioned cooling (slow)
benefits from longer
integrated times.