3.4.6 Additional heating step
See also Appendix: 2-step heating
Table 16
Designation
Values
Meaning
Hysteresis
0,3 K
0,5 K
0,7 K
1 K
1.5 K
Interval between the switch-
off point (set point value) and
the re-switch on point (Set
point value – hysteresis).
The hysteresis prevents
constant switch on/off.
Feedback of hysteresis
controlled with switch point
None
0,1 K/min
0,2 K/min
0.3 K/min
The feedback causes a
gradual decrease in the
Hysteresis over time.
This increases control
accuracy.
The hysteresis is equivalent to
the programmed value for
each switch-off and is
gradually reduced by the
feedback process. The
hysteresis can reduce to 0
over prolonged periods of
switch-off.
At the next switch-on, it is
reset to the configured value.
Cyclical transmission of
additional heating system
No cyclical transmission
Every 2 min
Every 3 min
Every 5 min
Every 10 min
Every 15 min
Every 20 min
Every 30 min
Every 45 min
Every 60 min
How often should the
switching status of the
additional step be sent?