Operation Manual
Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 29 of 71
Continued:
Designation
Values
Meaning
Parameters for continuous additional step
Proportional band of
additional heating system
2 K, 2,5 K, 3 K
3,5 K, 4 K, 4,5 K
5 K, 5,5 K, 6 K
6.5 K, 7 K, 7.5 K
8 K, 8.5 K
Prof. setting to adapt the
control response to the room.
Large values cause finer
changes to the actuating
values with the same control
deviation and a more precise
control than smaller values.
Transmission of actuating
value of additional heating
system
On change by 1%
On change by 2 %
On change by 3 %
On change by 5 %
On change by 7 %
On change by 10 %
On change by 15 %
After how many % change*
in the actuating value is the
new value to be sent.
Small values increase control
accuracy but also the bus
load.
*Change since last sending