Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 34 of 71
3.4.9 Device settings
Table 19
Designation
Values
Meaning
Direction of control action
of valve
Normal (closed with pushed
tappet)
Inverted, (open with pushed
tappet)
For all standard valves
Adjustment to inverted valves
Strategy for identifying
valve
Standard
Standard identification for
most valve models.
Automatic
Only for devices from
software V63.
The valve is closed with a
pre-defined force (see below,
"Closing force for"
parameter).
The 0 % position is checked
at the valve with every run
and the “100 % open”
position is measured at the
valve.
With defined valve stroke
Only for devices from
software V63.
The 0 % position is checked
at the valve with every run
and the
100 % (open) position is
established from the set
stroke.