Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 37 of 71
Continuation:
Designation
Values
Application
Function of Object 6
Increase or decrease set point
value
Determines maximum actuating
value
Sends the actual valve position
Change set point value in
increments via Object 6
Object 6 Determining the
maximum actuating actuating
value
Object 6 sends the current
valve position during the
tappet movement.
This setting is most suitable
for diagnostic operations
Designation
Values
Meaning
Transmission of maximum
actuating value
when internal actuating value
is higher than the received
Every 2 min
Every 3 min
Every 5 min
Every 10 min
Every 15 min
Every 20 min
Every 30 min
Every 45 min
Every 60 min
Object 6 will only send if all
other actuators have a smaller
actuating value
Object 6 sends its actuating
value cyclically and starts a
new calibration
Transmission of actual
valve position
Does not send
At change of 1%
At change of 2 %
At change of 3 %
At change of 5 %
At change of 7 %
At change of 10 %
At change of 15 %
Sends the new valve position
as soon as it has changed
since the last sending by the
configured amount.
At the end of positioning, the
achieved value is sent
regardless of the configured
interval.