Operation Manual
Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 40 of 71
3.4.12 Own characteristic valve curve
Prof. setting for special valves.
This parameter appears only when an internal characteristic valve curve has been selected
from the "Unit settings" page.
The actuator response can be accurately adjusted using the characteristic valve curve
(manufacturer’s documentation).
This parameter enables the Cheops control to be adjusted on a valve at 9 points of the
characteristic curve (10%.....90%). A certain flow is reached for each point at a certain % of
the valve stroke.
Table 22
Designation
Values
Meaning
Valve position in % for 10%
volume flow (1..99)
1..99 (10)
At what % valve stroke is a
volumetric flow of 10%
reached?
Valve position in % for 20 %
volume flow (1..99)
1..99 (20)
At what % valve stroke is a
volumetric flow of 20%
reached?
Valve position in % for 30 %
volume flow (1..99)
1..99 (30)
At what % valve stroke is a
volumetric flow of 30%
reached?
Valve position in % for 40 %
volume flow (1..99)
1..99 (40)
At what % valve stroke is a
volumetric flow of 40%
reached?
Valve position in % for 50 %
volume flow (1..99)
1..99 (50)
At what % valve stroke is a
volumetric flow of 50%
reached?
Valve position in % for 60 %
volume flow (1..99)
1..99 (60)
At what % valve stroke is a
volumetric flow of 60%
reached?
Valve position in % for 70 %
volume flow (1..99)
1..99 (70)
At what % valve stroke is a
volumetric flow of 70%
reached?
Valve position in % for 80 %
volume flow (1..99)
1..99 (80)
At what % valve stroke is a
volumetric flow of 80%
reached?
Valve position in % for 90 %
volume flow (1..99)
1..99 (90)
At what % valve stroke is a
volumetric flow of 90%
reached?
The values in brackets indicate a linear valve.