Operation Manual
Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 47 of 71
5 Appendix
5.1 Determining the current set point value
The current set point value can be adapted in line with certain requirements by selecting the
operating mode.
The operating mode can be specified by Objects 3…5.
There are two methods available:
5.1.1 New operating modes
If on the parameter page “operating mode”, new operating mode is selected by the " Objects
to select operating mode" parameter, the current operating mode can be defined as follows:
Table 23
Pre-selected operating
mode Object 3
Presence
Object 4
Window status
Object 5
Current operating
mode Object 10
Any
Any
1
Frost/heat protection
Any
1
0
Comfort
Comfort
0
0
Comfort
Standby
0
0
Standby
Night
0
0
Night
Frost/heat protection
0
0
Frost/heat protection
Typical application: In the mornings Object 3 activates "Standby" or "Comfort" mode and in
the evenings "Night" mode via a timer (e.g. TR 648).
During holiday periods, Object 3 also selects frost / heat protection via another channel of the
timer.
Object 4 is connected to a presence indicator. If a presence is detected, Cheops control
switches to Comfort mode (see Table).
Object 5 is connected to a window contact. As soon as a window is opened, Cheops control
switches to frost protection mode.