Operation Manual

Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 48 of 71
5.1.2 Old operating modes
If on the parameter page, old operating mode is selected by the " Objects to select operating
mode" parameter, the current operating mode can be defined as follows:
Table 24
Night
Object 3
Comfort
Object 4
Frost / heat protection
Object 5
Current operating
mode Object 10
Any
Any
1
Frost/heat protection
Any
1
0
Comfort
Standby
0
0
Standby
Night
0
0
Night
Typical application: In the mornings "Standby" mode and in the evenings "Night" mode is
activated via a timer.
During holiday periods, Object 5 selects frost / heat protection via another channel on the
timer.
Object 4 is connected to a presence indicator. If a presence is detected, Cheops control
switches to Comfort mode (see Table).
Object 5 is connected to a window contact. As soon as a window is opened, Cheops control
switches to frost protection mode.
The old method has two advantages over the new method:
1. To switch from Comfort to Night operating mode, 2 telegrams (2 timer channels if
necessary) are required.
Object 4 must be set to 0 and object 3 to 1.
2. If during periods when "Frost / heat protection" is selected via the timer, the window
is opened and then closed again, the "Frost / heat protection" mode is cleared.