Operation Manual
Continuous valve actuator CHEOPS control
theben
As of: Jul-11 (Subject to change without notice) Page 52 of 71
5.3.1 Connections
Table 27
Name
Colour
Function
BUS
Black (-)
EIB bus line
Red (+)
E1
Yellow
Binary input for window contacts(e)
Green
E2
White
Binary input for presence indicator, presence key or analogue input
for external temperature sensor
Brown
5.3.2 Input E1
E1 is used exclusively for window contacts (if present).
The window contacts can be connected to E1 directly and without additional supply voltage.
On the "External interface" parameter page, the Type of connected window contact
(Opener/closer) can be set.
When the "Open" window position is detected, Cheops control switches to frost operating
mode.