User guide

M6-MW
M6-MWFG
Semi-welded plate heat exchanger
Applications
Heating and cooling of aggressive media. Duties in refrigeration
installations.
Standard design
The plate heat exchanger consists of a pack of corrugated
metal plates with portholes for the passage of the two uids
between which heat transfer will take place.
The plate pack is assembled between a x frame plate and a
movable pressure plate and compressed by tightening bolts.
The semi-welded plates combine the exibility and service-
ability of the gasketed heat exchangers with the assurance
against leakage of the welded heat exchangers. In the plate
arrangement, every other channel is welded, and every other
channel is gasketed. The number of plates is determined by
the ow rate, physical properties of the uids, pressure drop
and temperature program. The plate corrugations promote
uid turbulence and support the plates against differential
pressure.
The semi-welded plate heat exchanger is provided with
gaskets specically designed to resist aggressive media.
The non-aggressive media ows in the gasketed channels.
This construction means that it can easily be dismantled, for
example for exchanging gaskets or for inspection and cleaning
of the gasketed channels.
Corrosion-resistant plate materials, the absence of pressure
retaining welds, double gasket seals, and a exible yet vibration
resistant design - to assure long life and trouble free operation.
The frame plate and the pressure plate are suspended from
an upper carrying bar and located by a lower guiding bar,
both of which are xed to a support column. Connections are
located in the frame plate or, if either or both uids make more
than a single pass within the unit, in the frame and pressure
plates.
Typical capacities
Liquid ow rate
Up to 16 kg/s, depending on media, permitted pressue drop
and temperature program.
Refrigeration duties
10-70 RT/35-250 kW
Plate types
M6-MW
Frame types
FG and FD
Cross section of a semi-welded plate heat exchanger

Summary of content (10 pages)