Operating Manual
Chapter 3 Set up Level, Level Alarms, and Volume Accu-Wave 
3-2 TN Technologies 
Set up Primary Measurement (Distance or Level) 
During the initial setup, you will be asked to enter the distances to the highest and lowest 
points on the tank that you need the gauge to “see.” Thus, you need to measure these 
distances on your tank relative to the reference line marked on the sensor. Note the high 
and low measurement points do not have to be the top and bottom of the tank. These points 
are used to establish the range of interest (ROI) as shown in Figure 3.2. The ROI defines 
the range over which the gauge looks for the echo from the process material surface. The 
ROI may be overridden in the “Radar fine tuning” menu (refer to Chapter 5). 
You must set up either distance or level as the primary measurement before setting up 
other measurements. The Accu-Wave software numbers the measurements with 
measurement #1 being the primary measurement. It is good practice to make a list of how 
you set up each measurement and its measurement number, and to have this list available 
for future reference.  
Select distance as the primary measurement if you are interested in the distance from the 
zero distance point to the surface of the process material as shown on the right-hand side 
of Figure 3.2. Select level as the primary measurement, if you are interested in the distance 
from the zero level point to the current level of the surface of the process material as 
shown on the left-hand side of Figure 3.2. 
The Zero Distance, Maximum Distance, and Zero Level points are all measured from the 
reference line (inscribed in the sensor housing) downward to the appropriate point on the 
tank. The Maximum Level point is measured from the Zero Level point upward. 
Figure 3.2 Primary Measurement – Distance or Level 
After setting up the required entries for the primary measurement, you can set up 
additional measurements (for example, volume, percent full and percent empty) using the 
“Set Up Additional Measurements” menu discussed in Chapter 4. 
“Set up Level” Menu 
The “Set up Level” portion of the “Set up Level, Level Alarms, and Volume” Menu is 
used to set up the primary measurement, either level or distance, for your gauge. These 
menu items are given in the table below in the order they appear as you scroll through the 
Reference Line 
(marked on sensor) 
Maximum Distance 
Zero Level 
Maximum Level 
Range of Interest 
(ROI) for level 
Range of Interest 
(ROI) for distance 