Operating Manual
Chapter 3 Set up Level, Level Alarms, and Volume Accu-Wave 
3-4 TN Technologies 
“Set up Level” Menu (continued) 
Display  Comments 
If the primary measurement is distance, the following two menu items are shown. 
Distance REF LINE to 
zero distance point 
0.000 ft {.6910} MIN 
 NEXT↓↓ HELP→→ 
Enter the distance from the reference line on the 
sensor housing to the zero distance point, the closest 
point to the sensor to be measured. In most cases the 
zero distance point is the top of the tank. The readout 
will be zero at the zero distance point. Above this 
point, the readout will be negative.  
REF LINE to maximum 
distance to be 
measured 0.000 ft 
 NEXT↓↓ HELP→→ 
Enter the distance from the reference line on the 
sensor housing to the maximum distance point, the 
farthest point from the sensor, to be measured. 
If the primary measurement is level, the following two menu items are shown. 
Distance REF LINE to 
zero level point 
0.000 ft {115.1 MAX} 
 NEXT↓↓ HELP→→ 
Enter the distance from the reference line on the 
sensor housing to the point on the tank where the 
level measurement readout should display zero. The 
zero level point does not have to be at the bottom of 
the tank. Below the zero level point, the readout will 
be negative. 
Maximum level 
to be measured 
0.000 ft {x.xxx MAX} 
 NEXT↓↓ HELP→→ 
Enter the highest possible level to be measured 
relative to the zero level point. The value displayed as 
{x.xxx MAX} is calculated based on the entry for the 
zero level point. The gauge will not measure reliably 
above this level. 
Position of decimal 
in readout 1 000.0 
{ft level} 
 NEXT↓↓ ←←CHANGE→→ 
Press ← or → to move decimal point to the desired 
position in the display readout for the primary 
measurement (level or distance). 
Note: The next two menu items define the levels (or distances) corresponding to 
the maximum and minimum current outputs. The default range for the 
current output is 4.0 mA to 20.0 mA. To change the max or min current 
output, use the “Modify or reassign current output” menu (see Chapter 6.) 
Meas #1 reading for 
20.00 mA output: 
0.000 ft level 
xx.xx assume NEXT↓↓ 
Enter level or distance which corresponds to the 
maximum current output. For level, “Maximum 
level” is the default (assumed) value. For distance, the 
value (Maximum Distance – Zero Distance Point) is 
the default. If the entry is exactly zero, the default 
(assumed) value is used. 
Meas #1 reading for 
4.000 mA output: 
0.000 ft level 
 NEXT↓↓ 
Enter level or distance which corresponds to the 
minimum current output. The default value is 0.0. For 
level, this is the “Zero Level Point,” and for distance, 
this is the “Zero Distance Point.” 