Operating Manual
Chapter 3 Set up Level, Level Alarms, and Volume Accu-Wave 
3-10 TN Technologies 
The next table presents those menu items specifically related to controlling a relay as an 
alarm indicator. As noted in the Comments column, several of the menu items are only 
displayed if options have been enabled in the “Special functions” menu, see “Special 
Functions” on page 8-19. 
“Set up Alarm” Menu (continued) 
Relay Indicator Related Items 
Display  Comments 
alarm relay 1 set 
delay 0 seconds 
(0-255 s after 
alarm) NEXT↓↓ 
Only displayed if “alarm relay delay times” have been 
enabled in “Special functions” menu (see page 8-19). 
Alarm condition must persist for the time entered for 
alarm to be activated. 
alarm relay 1 clear 
delay 0 seconds 
(0-255 s after alarm 
has cleared) NEXT↓↓ 
Only displayed if “alarm relay delay times” have been 
enabled in “Special functions” menu (see page 8-19). 
Alarm clear condition must persist for the time 
entered for alarm to be cleared. 
Do not use latching 
mode with relay 1. 
Change to “Do”→→ 
Continue as is.↓↓ 
Only displayed if relay latching has been enabled in 
“Special functions” menu (see see page 8-19). When 
latch mode is enabled for a relay, the relay remains in 
alarm state even after the actual alarm is clear. The 
relay is cleared by a “Clear alarms” command (see 
page 7-3) or when system has been powered off. 
Relay 1 turns on 
when alarm occurs. 
Change to “off”→→ 
←←Exit alarm 1 setup. 
Only displayed if a relay alarm indicator is selected as 
the alarm indicator. Non-relay indicators include 
zeroing current output, flashing display, or activating 
commands.  
After each alarm is set up, you will have the opportunity to set up another alarm, up to 16 
alarms. Always keep a written record of how each alarm is set up. You can add a relay 
board at any time. You can set up more alarms later using the “Set up additional 
measurements” menu, see Chapter 4. 
Example: High Limit Level Alarm 
This example illustrates how to set up a high limit level alarm using a Set Point/Clear 
Point alarm configuration. The primary measurement has been set up as level with the 
“Distance REF LINE to zero level point” set at 22.5 ft and the “maximum level to be 
measured” set at 18.0 ft. It is desired to activate a process alarm when the process material 
level increases to 15.0 ft (relative to the zero level point) and to clear the alarm when the 
process material level decreases to 13.0 ft. This configuration is illustrated in Figure 3.6.  










