Operating Manual
Chapter 6 Cuurent Outputs, Relays, and Alarms Accu-Wave 
6-6 TN Technologies 
By default all 16 alarms are assigned to the primary measurement, measurement 1. 
“Assign Alarms to Measurements” Menu 
Display  Comments 
Assign alarms to 
measurements→→ 
 NEXT↓↓ 
Menu subgroup heading. Press → to access menu 
items, press ↓ to scroll to next “Alarms” menu 
subgroup. Only displayed if you have set up one or 
more additional measurements (other than primary).  
#1 alarm monitors 
measurement 1 
ft level 
 Continue↓↓ Change→→ 
Press → to scroll through the list of measurements 
that have been set up until the one you want appears. 
Message on third line indicates the measurement type 
corresponding to the measurement number. 
Note:  By default configuration, all 16 alarms are assigned to the measurement 1 
(the primary measurement). Above menu item is repeated for alarms 2 – 15. 
Press “EXIT SETUP” to save entries and return to the measurement display 
if you do not want to assign more alarms. 
#16 alarm monitors 
measurement 1 
ft level 
 Continue↓↓ Change→→ 
Scroll through the list of measurements that have 
been set up until the one you want appears. 
Assign Relays to Fault, Warning and Mode Alarms 
Relays can be assigned to fault alarms, warning alarms and mode alarms using the menu 
items shown in the table below. The “Assign relays to warning alarms and fault alarms” 
menu items apply to warning and fault alarms, while the “Assign relays to mode alarms” 
menu items apply to the mode alarms. 
The “Assign relays…” menu headings are somewhat misleading as these menus are used 
to assign any of the alarm indicators (controlling relays, flashing the measurement display, 
zeroing current output, or executing a command) to the fault, warning, or mode alarms. 