ACU-STEAM HUMIDISTAT, version A
Features 
 State of Art digital RH sensor
 ROOM or DUCT mounting
 Reprogrammable Microcontroller
 Potentiometer Set-point setting
 Out-door temperature sensor for Set-point Reset
 Green (ON/OFF) and Red (warning) status LEDs
Specifi cations
Set-point range. . . . . . . . . . . . . . . 20% to 50% Relative Humidity
Accuracy. . . . . . . . . . . . . . . . . . . . ±4.5%, without calibration 
Linearity . . . . . . . . . . . . . . . . . . . . ±1% in the Set-point range    
Differential % RH. . . . . . . . . . . . . ±2%
Outdoor Temp. Reset Range  between -9 ˚F (-23 ˚C) to 27 ˚F (-3 ˚C)
 Outdoor reset Temperature vs.   Set point change
 28 ˚F (-2 ˚C) and warmer      No change       
 27 ˚F (-3 ˚C) to 23 ˚F (-5 ˚C)  42% max,  
 22 ˚F (-6 ˚C) to 18 ˚F (-8 ˚C)  38% max,  
 17 ˚F (-9 ˚C) to 12 ˚F (-11 ˚C)  34% max,  
 11 ˚F (-12 ˚C) to 5 ˚F (-15 ˚C)  30% max,  
 4 ˚F (-16 ˚C) to -2 ˚F (-19 ˚C)  26% max,  
 -3 ˚F (-20 ˚C) to -9 ˚F (-23 ˚C)  22% max,  
 -9 ˚F (-23˚C) and colder      20% max.     
NOTE: these ranges can vary by ±2 %.
The Outdoor Temperature sets the maximum set point of RH internally. 
If the Dial position is higher, the actual set point will be limited as above.