Drawing

Halogen Free
Features & Benefits:
Meets UL 514B and CSA C22.2, No. 18.3 for liquid-tight fittings
Full compliance to IEC 61386-1, -23 requirements, CE Certified
Trade sizes from ” to 2” (12mm to 63mm)
Insulated throat protect wire jacket from damage
Straight, 45° and 90° conduit bodies
NPT and ISO Metric Thead Types
Coordinated performance with T&B Liquidtight Systems Flexible Metallic Conduits
Ingress protection ratings aligned with industrial enclosures
Safe Edge® ground cones provide superior bonding
Double Bevel Sealing Ring eases assembly and insures lliquid-tight performance
Heat curled insulators protect wire sheathing from damage
Applications:
Typical applications where severe corrosion protection is required including water/
wastewater, food & beverage, salt environments, chemical processing, etc.
Used where liquid tight flexible metallic raceway is installed in corrosive outdoor or indoor
locations, and exposed to continuous or intermittent moisture
Used to positively bond flexible liquid-tight flexible metallic conduit to boxes or enclosures
Ideal for use with T&B Liquidtight Systems LFMC types LT4GE, LT6GE and LT6FE
Liquid-tight applications against water, oils, cutting fluids, mild acids
For use in electrical circuits up to 1,000 V
Suitable for use in Class 1 Division 2, Class 2 Division 1 & 2 Hazardous Locations per
NEC® Section 500
Construction / Material / Finish:
Trade sizes ” to 2” Steel Steel 316
Zinc Plated steel ground cones, optional stainless steel 316
Thermoplastic nylon seal rings and insulators
Halogen Free seal rings, insulators and seal gaskets
Machined locknuts with teeth for vibration resistance, supplied separately
Environment ratings:
Working Temperature:
UL: Gen: -20 to +105°C (-4 to +221°F)
CSA: Gen: -20 to +105°C (-4 to +221°F)
IEC/CE: Gen: -45 to +150°C (-49 to +302°F) Staticxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxx Gen: -25 to +105°C (-13 to +221°F) Dynamic
Chemical Resistance Guide:
See Publication TDS000081 (Fittings: Stainless Steel 316 & PA66 Polyamide)
SSee Publication TDS000117 (Liquid Tight Flexible Metal Conduits)
Conforms to:
UL 514B, Fittings for Cable and Conduit
E23018 (-6 SST Ground Cone: 1/2” and 3/4” only)
CSA C22.2, No. 18.3, Outlet and Conduit Boxes, Fittings and Accessories
File: LR-4484
IEC/EN 61386-1, -23, Conduit Systems for Cable Management
EU DoC: EC-012-7189
RoHS (Restriction of Hazardous Substance directive)
NEMA FB-1 (Fittings and Conduit Bodies)
JIC EGP1 (Electrical standard for GP machine tools)
JIC EMP1 (Electrical Standard for Mass Production Engineering)
Federal Specification A-A 50552 (Fittings for flexible conduit)
Federal Specification H-28 (Threads)
Ingress Protection:
Provides “Ingress Integrity” between enclosures, fittings, conduits & seals when using
Series 5300SST6 liquid-tight fittings and T&B Liquidtight Systems LFMC
Covers all trade sizes from ” to 2” (12mm to 63mm)
Ingress ratings require use of Series 5260 Seal Gaskets
ISO Metric Thread fittings supplied with Seal O-Rings as standard
UL & NEMA system ingress ratings:
UL Listed type ratings tested to UL 50/50E requirements with UL Listed LFMC
UL File No.: E23018
Indoor: Type 4, 12, 13
Outdoor: Type 3, 3R, 4, 4X
CSA C22.2, No. 94.2: Type 3, 3R, 4, 12, 13
NEMA 250: Type 3, 3R, 4, 4X, 12, 13
IEC system ingress ratings:
IP Ingress Protection per IEC 60529 requirements
IEC Ingress Ratings: IP66, IP67
Standards requirements:
Designed to UL 514B and CSA C22.2, No. 18.3 test requirements including:
Assembly, Pull, Resistance, Oil spray, Polymer durability, Flammability Coating thickness,
Current withstand
Meets all IEC/EN 61386-1, -23 standard requirements including:
Impact resistance - Code 3 Medium; 6 Joules
Tensile strength - Code 3 Medium; 500 N/2 min.
Lower and upper temperatures
IP protection against solid and liquids
Stainless steel 316 liquid-tight and
system solutions for the most
demanding corrosive environments
Certifications / Standards:
1
TECHNICAL DATA SHEET
Liquid-tight fittings - Series 5300SST6
For liquid-tight flexible metallic conduit

Summary of content (2 pages)