Installation Manual
IS--0459
IS--ECS
January 2006
Page1of2
R
Installation Instructions
ECS
Jacketed Cable Sealing Kit
for Jacketed Concentric Neutral Shielded Cable
200 ECS -- Cable O.D. Range 0.80”--1.50” (20--38mm)
600 ECS -- Cable O.D. Range 1.28”--2.30” (32--58mm)
CONTENTS: Cold Shrink T ube, 3 -- Pieces Mastic Strip, Installation Instructions.
DANGER
All apparatus must be de--energized during installation
or removal of part(s).
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result
in its failure.
Inspect parts for damage, rating and compatibility with
mating parts.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
IMPORTANT: Cutback dimensions should be checked; exposed length of semi--con between cable jacket and device end
should be no more than 2--1/2” (64mm).
STEP A
Remove cable jacket for a distance of 2--1/2” (64mm) more
than cutback length for the cable semicon as stated in the
manufacturer’s instructions.
Wrap the first mastic strip around the cable jacket 0” to 1/4”
from the end. Stretch as needed to completely encircle the
cable. Bend the ground wires back over the mastic and
along the jacket, pressing them into the mastic.
IMPORTANT: Ground wires should not touch each other
when pressed into the mastic to prevent water ingress.
Ground Wires
Cable Jacket
Mastic
0”--1/4” (0mm--6mm)