Installation Manual
INSTRUCTION SHEET
for Copper Clad Steel
Ground Rod Connectors
INSTRUCTIONS:
1. Cable end should be clean. Wire brush or clean with emery
cloth if necessary and insert into connector.
2. Copper clad ground rod to be wire brushed lightly before assembling connector to rod.
3. Table below contains installing die. Insert connector in die and compress between markings.
GENERAL:
• Made of high conductivity copper.
• UL and CSA listed for copper coded cables.
• Approved for Direct Burial.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
TA00987 B
Page 1 of 1
© 2014 Thomas & Betts. All Rights Reserved.
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability
of this product for the user's intended application. Thomas & Betts warrants that this product will be free from defects in materials or
workmanship for a period of two (2) years following the date of purchase. Upon prompt notication of any warranted defect, Thomas & Betts
will, at its option, repair or replace the defective product. Misuse, misapplication or modication of Thomas & Betts Products immediately voids
all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL
OTHER WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY
OR FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE
WARRANTY IS LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO CIRCUMSTANCES WILL
THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Cat. No.
Ground
Rod
Cable Size
Hex*
Die Code
GR12-306 1/2”
(1) 3/0, 2/0, 1/0, #2, #4, #6 OR
(2) #2, #4, #6
87H
GR58-406 5/8”
(1) 4/0, 3/0, 2/0, 1/0, #2, #4, #6 OR
(2) #2, #4, #6
87H
GR34-4010 3/4”
(1) 4/0, 3/0,2/0 OR 1/0 OR
(2) #2, #1, OR 1/0
99H
CAUTION
Using improper installing die may result in defective connection.
*
Installing tools 13100A, TBM14CR-LI, TBM14M, TBM15CR-LI, TBM15, or TBM15I
two compressions all connectors.